Double Tap Connections on Breakers

Double Tap Connections on Breakers.  Reuben Saltzman is a second-generation home inspector with a passion for his work. Naturally, this blog is all about home inspections and home-related topics in the Twin Cities metro area. In addition to working at Structure Tech, he is also a licensed Truth-In-Sale of Housing Evaluator in Minneapolis, Saint Paul and several other cities.

Double tapped circuit breakers are one of the most common electrical defects that I find while doing home inspections in Minneapolis and Saint Paul, and they’re usually one of the easiest defects to correct.  Today I’ll explain what double tapping is, when it is and isn’t a problem, why it’s a problem, and how to correct this condition.

I didn’t consult with an attorney before writing this article, so I feel like I should add a disclaimer before giving any electrical how-to information:  Don’t do any of this work if you’re not qualified.  You could get electrocuted or start a fire.  This is only an overview.

Definition: When I say ‘double tap’, I’m actually not using the correct terminology; this is just what a lot of home inspectors say when two conductors are connected under one screw or terminal inside a panelboard.  There is no official term for this, so double tap works for me.  Sometimes this refers to two conductors at one circuit breaker, other times it refers to two conductors connected under one screw at the neutral bar.  Today I’ll be discussing two conductors connected to a single circuit breaker.

When it’s NOT a defect: Double tapped wiring is ok if the circuit breaker is designed for two conductors.  If a circuit breaker is designed for two conductors, it will say so right on the circuit breaker, and the terminal of the circuit breaker will be designed to hold two conductors in place.  The circuit breaker shown below is an older Square D designed to accept two conductors.  I highlighted and enlarged the portion of the label that says two conductors can be attached.  This is acceptable.  The only manufacturers  that make circuit breakers that are designed to hold two conductors are Square D and Cutler Hammer… but not all of their circuit breakers can be double tapped.

Here’s a newer type of Square D circuit breaker – instead of putting a bunch of text on the front of the circuit breaker, they now just have a little picture on the front of the breaker.

 

 

 

 

 

 

 

They now  put the text on the side of the breaker.

 

 

 

 

 

When it IS a defect: This is a defect when the circuit breaker isn’t designed for two conductors; most aren’t.  It doesn’t matter if it’s just a simple doorbell transformer wire that’s added on to the circuit breaker – the issue isn’t about the load imposed on the circuit, it’s about the physical connection.

 

Why it’s a problem: If the circuit breaker isn’t designed to hold two conductors, the conductors could come loose at some point in the future, even if they feel very tight today.  Loose conductors can lead to


 

How to fix: The fixes I’m going to list below are a few common ways of dealing with double tapped circuit breakers.overheating, arcing, and possibly a fire.

 

 

Pig Tail:  This is the most common repair, and it’s ridiculously simple.  The offending conductors simply get disconnected from the circuit breaker, connected to a single conductor with a wire nut, and that single conductor gets connected to the circuit breaker.   Now, I know what you’re thinking: “What’s so tough about that?”  The answer is nothing.  This is a quick and easy fix.

 

Different Circuit Breaker Another simple repair would be to replace the circuit breaker with a type that isdesigned for two conductors, as long as the panel is designed for it.  This would be more involved than the pig tail repair, and I don’t know why anyone would want to do this, but it would certainly be acceptable.

If there are more problems going on besides just a double tap, the repair might get more involved.  For instance, if a homeowner finished off a basement and added a circuit for the basement bedroom on to the circuit breaker for the bathroom receptacles, simply adding a pig tail for the wires wouldn’t be a proper repair, in part because the bathroom receptacles can’t be on a shared circuit (and the bedroom circuit needs AFCI protection – more on that another day).   In this case, the conductors would need to be split off on to two separate circuit breakers.  There are a few ways to do this.

Add A Circuit Breaker If there is room in the panel, another circuit breaker can be added, and the conductors split off to the two different circuit breakers.

 

Install A Tandem Breaker If the panelboard is designed to use tandem breakers and a tandem breaker can be properly used in lieu of the offending circuit breaker, this is another acceptable fix.  This is basically a way to install two circuit breakers in one space.

If a panel will accept tandem breakers, it will say so inside the panel, and the specific locations where tandem breakers can be used will be identified.  A panel may allow all tandem breakers, no tandem breakers, or some tandem breakers.  The photo below shows a panel that allows some.  As you can see, eight more circuits could be added to this panel, as there are currently no tandem breakers being used.  This would take some shuffling around, but it wouldn’t be a big deal to do.

 

When none of the above solutions are possible, the repair might involve replacement of the panel with a larger one, or the addition of a subpanel.  This would obviously get much more expensive.

 

Electrical Basic Tips

Electrical Basic Tips.  ELECTRICAL Wiring codes and their origin

Wiring codes are intended to protect people from electrical shock and fire hazards .The very first electrical codes started in 1881 in New York to regulate the installations of electrical lighting. Since 1927 , the Canadian Standards Association also know as ( CSA ) has produced the (Canadian Safety Standards for Electrical Installations ) which became the basis for all provincial electrical codes.

The Canadian and the U.S. National standards differ occasionally in technical detail however they deal with the same physical phenomena and have similar objectives. As part of the North American Free Trade Agreement (NAFTA) program, U.S. and Canadian standards are slowly converging toward each other, in a process known as harmonization.

The difference between electrical insulators and conductors

In many materials, the electrons are tightly bound to the atoms. Wood, glass, plastic, ceramic, air, cotton — these are all examples of materials in which electrons stick with their atoms. Because the electrons don’t move, these materials can’t conduct electricity very well, if at all. These materials are electrical insulators..

Most metals, however, have electrons that can detach from their atoms and zip around. These are called free electrons . The loose electrons make it easy for electricity to flow through these materials, so they’re known as electrical conductors . They conduct electricity. The moving electrons transmit electrical energy from one point to another.

How circuit breakers/fuses work

Circuit breakers ( or the alternative , fuses ) may be one of the most important safety devices in your home. Whenever the wiring in your home or building has too much current flowing through it these devices cut the power until the problem can be fixed. Without these devices the potential for fires and other accidents resulting from simple wiring problems or equipment failures would be huge. The problem with fuses is they only work once . When you blow a fuse, it burns up the wire inside the fuse and you have to replace it with a new one. A circuit breaker on the other hand , closes the circuit when the current climbs to unsafe levels, but it can be reset and used over and over again.

GFCI ( Ground Fault Circuit Interrupter )

GFCI receptacles were designed to protect you from electrical shock. A GFCI monitors the amount of current flowing from the hot wire to the neutral wire. If the receptacle detects any imbalance in the current , it trips the circuit. They are designed to react as quickly as one-thirtieth of a second and can sense a mismatch as small as 5 milliamps. Building codes are now requiring that receptacles in potentially wet areas ( IE. Around bathroom/kitchen sinks or outside ) be GFCI protected for safety reasons. So let’s say you are outside with your power saw and it is raining. You are standing on the ground, and since the saw is wet there is a path from the hot wire inside the saw through you to the ground . If electricity flows from hot to the ground through you, it could be fatal. The GFCI can sense the imbalance in the current because not all of the current is flowing from hot to neutral as it expects — some of it is flowing through you to the ground. As soon as the GFCI senses that, it trips the circuit and cuts off the electricity.

Aluminium wiring

Aluminium wiring became popular in North America from the late 60’s to the mid 70’s due to the rising cost of copper. Aluminium wiring requires a lager conductor than copper due to the fact that it has greater resistance. For example , on a typical 15 amp circuit you would use a 14 gauge copper wire ( used for most lighting circuits ) where you would need a 12 gauge aluminium wire although local building codes may vary. Aluminium conductors were originally used with wiring devices intended for copper wires. This could cause defective connections unless the devices were designed to address problems in joining dissimilar metals.

Because of improper installation and design, some of the wiring junctions overheated under heavy current load and caused fires. Revised standards were designed to reduce these problems nonetheless aluminium wiring for residential applications has acquired a bad reputation and is no longer in use. Aluminium conductors are still used for power distribution and large feeder circuits, because they cost less than copper wiring, and weigh less, especially in the large sizes needed for heavy current loads. Aluminium conductors must be installed with compatible connectors.

Your Barrie Home inspector will check circuits in every room,  inspect your service entrance conductors and inspect the interior of your main panel board if new wiring has been added.

Aluminum Wiring Hazards and Solutions

Aluminum Wiring Hazards and Solutions.  Primarily in the 1960s and 1970s, many electrical contractors used aluminum wiring instead of copper wiring as a way to save money and lower construction costs. However, a number of electrical fires have been attributed to aluminum wiring. Many building codes have been rewritten to not allow the use of aluminum wire for branch circuit wiring in houses.

Copper vs. Aluminum — The Test Results are in! Tests have demonstrated aluminum wiring has inherent properties that make it more susceptible to fires when it was not installed correctly. Here are some of the problems with using aluminum wiring to conduct electricity. Aluminum does not conduct electricity as well as copper. An aluminum wire generates more heat. Aluminum is more brittle than copper. Wire is more likely to break or crimp if it is brittle. Arcing can occur if a wire breaks or crimps. This can cause very high temperatures inside the wall or ceiling Aluminum is more likely to corrode than copper. Aluminum will oxidize if it comes in contact with moisture. This oxidation removes the pure aluminum and makes the wire thinner. A thinner wire creates more heat when electrical current is running through it. Oxidation also causes the wire to expand, puts pressure on the protective plastic coating on the wire, and can cause the plastic to split. If any of these occur, arcing may result which can cause fires. Aluminum expands and contracts more than copper. This puts additional stress at all connections such as outlets and switches. If these become loose, arcing can occur at these points. If contemplating buying an older home with aluminum wiring or updating a home with aluminum wiring, contact a certified electrician to gain their expertise and opinion regarding the dangers of aluminum wiring.

State Farm believes the information contained in the Good Neighbor House is reliable and accurate. We cannot, however, guarantee the performance of all items demonstrated or described in all situations. Always consult an experienced contractor or other expert to determine the best application of these ideas or products in your home.
Between 1965 and 1973, aluminum wiring was used to install electrical branch circuits in about 1.5 million homes in the United States and Canada. Subsequent fires in some of these homes were attributed to faulty aluminum wire connections. During this period, studies conducted by the National Fire Protection Association, in conjunction with the U.S. Consumer Products Safety Commission, revealed that homes using aluminum wires manufactured before 1972 are 55 times more likely to have one or more electrical connections reach fire hazard condition than homes wired with copper. Aluminum wiring in itself is not dangerous. Aluminum wiring, when properly installed, can be just as safe as copper. But if it has not been installed properly, the connections-where the wires join to the outlets and switches- can present a fire hazard.

How to Tell The wiring that is of concern involves the circuit wiring to your outlets and light switches, and to appliances that us 115 volt current, such as furnace and washing machine. It is a single-strand, solid aluminum wire, silver in color as opposed to the characteristic copper wiring color. Most homes of any vintage employ some aluminum wiring. Often service entrance cables from the street that run to the distribution panel and major appliance circuits (220v) are aluminum. The safety concerns are not with the cables, but rather with branch circuit connections involving the lighting and other 115 v circuits. The Problem Most problems arise with solid aluminum wire, sizes #10 and #12 gauge. These problems concern the ends, or terminations, of the aluminum wire, where they connect under the bonding screws. If the connections are improperly installed, there is a potential for intermittent, hot connections where the wires join to the outlets and switches. Again, the problem is with the connections, and not with the wiring itself. The main difficulty with connections using aluminum wiring is a phenomenon known as cold creep. Aluminums coefficient of expansion (how much it expands when electrical current passes through it) is higher than coppers. Simply put, when aluminum wiring warms up, it expands more than copper does, and when it cools down, it contracts more than copper does. This expansion and contraction, over time, will allow for loosening at the connections. Also aluminum wire needs to be larger than copper to carry the same amount of electricity. Because the wires are thicker, you cannot get the same tightness at the connections. Therefore, they may loosen more quickly. To make the problem worse, all metals oxidize or corrode in an oxygen environment. Copper oxidation forms as a conductor, while aluminum develops as a resistor. This resistance causes heat. Oxidation accelerates when two unlike metals are in contact with each other. This may be part of the source of increased resistance when aluminum wire joins to outlets or switches intended for copper. Eventually the wire may start getting very hot, melt the insulation or fixture its attached to, and possibly even cause a fire. Evaluation of Your Electrical System As mentioned above, aluminum wiring can be just as safe as copper when properly installed. Denver’s Building Department has always maintained-including during the years 1965 to 1977, when aluminum wiring was being installed nationwide- a force of electrical inspectors who themselves are licensed electricians and have worked diligently to ensure that all installations comply with local and national standards. Many of the incidents publicized from other parts of the country simply don’t occur here. Still, any potential electrical problem is a potentially serious problem.

There are several warning signs to look for that would suggest the possibility of connection problems. They are:
– Sparks emanating from outlets
– Warm-to-touch cover plates on outlets and switches
– Smoke coming from outlets, junction boxes or switches
– Lights that flicker for no apparent reason
– Melted insulation (plastic) at the connections
– Smell of burning plastic at outlets
– Light bulbs that burn out quickly, or shine unusually bright
– Blown fuses or tripped breakers for no apparent reason
– The size of your television picture shrinks

Making Sure Its Safe
If you are experiencing one or more of the above connection problems, or are otherwise concerned, we suggest that you hire a licensed electrician to check over the wiring for the following:
1. Outlets and switches directly attached to aluminum wiring shall be listed for that purpose. The device will be stamped with AL/CU or CO/ALR. The latter supersedes the former, but both are safe. These fixtures are somewhat more expensive than the ordinary ones.
2. Wire should be properly connected (wrapped at least way around the screw in a clockwise direction). Connections should be tight. While repeated tightening of the screws can make the problem worse, during the inspection it would pay off to have the electrician snug up each connection.
3. Push-in terminals (terminals where the connecting wire is pushed into a slot rather than wound around a screw) are an extreme hazard with aluminum wire. Any connections using push-in terminals should be redone with the proper screw connections immediately.
4. There should be no signs of overheating darkened connections, melted insulation, or baked outlets or switches. Any such damage should be repaired.
5. Connections between aluminum and copper wire need to be handled specially. Current Denver City Ordinance requires that the connections used must be specially marked for connecting aluminum to copper. The National Electrical Code requires that the wire be a connected together using special crimp device, with antioxidant grease (see Repair Options, over).
6. National Electrical Code, Sections 110-114 and 310-314 address electrical conductors of dissimilar metals and prohibit the use of unlisted twist-on connectors for connection of copper and aluminum wiring.

A Final Caution The United States Fire Administration reports that annually, of the nearly 800,000 residential fire nationwide, approximately 75,000 began in the homes electrical distribution system that is, in the circuit wiring, receptacles, switches, cords and plugs. When a part of this network fails or is misused, a fire may result. Many of these fires were attributed to old technology aluminum branch circuit wiring. Of the fires involving old technology aluminum branch circuit wiring, 75 percent of the incidents involved receptacles, 12 percent involved panel equipment terminals, and 10 percent involved twist-on connections. Fire investigators, including those of the Denver Fire Departments Fire Prevention and Investigation Division, determined that old technology aluminum-wired receptacles and twist-on connectors, when used with aluminum wire, were failure prone, even when installed carefully in accordance with the manufacturers instructions. Leave aluminum wiring safety improvements to licensed electrical contractors. Denvor Building Department electrical inspectors will monitor work done under City permit. Any time you suspect unusual heat or smoke generated from the electrical system in your house, do not hesitate to call 911 and request a Fire Company to respond and evaluate conditions. The safety of your family is of primary importance.

This article by the Denver Fire Department is brought to you by Napoleon Home Inspections – The Barrie Home Inspector

The Barrie Home Inspector will open panel and junction boxes looking for concealed aluminum wiring.  Ensure you know what your buying before committing to purchase.

Your Home Electrical System

Your Home Electrical System.  In many older residential areas, and practically all rural locations, the electrical supply is delivered to the property via overhead conductors strung on telegraph poles.  The high-voltage lines connect directly to the property through a transformer delivering main power.
Most residential buildings are supplied with 120/240-volt services.  This means that the cable assembly is made up of two un-grounded  (live or hot) conductors each supplying 120 volts, and one neutral or grounded conductor acting as the return.

The masthead, or gooseneck, as it is sometimes called, is at the top of the mast itself. Its purpose is twofold: first, to act as a rain cap to stop moisture from entering the conduit; and, second, to provide the bushings to prevent the individual conductors from being damaged by rubbing against the metal components. The masthead should be undamaged and securely fastened to the service mast.

Type-UF cable is rated for direct burial, and has outer sheathing that is resistant to moisture and damage from soil. This type of cable must be buried to a depth of 18 to 24 inches (depending on the location, as described in section/table 300.5 of the NEC) and, if embedded in rocky ground, must be installed in a manner that will not damage the cable. This cable still needs to rise  in a conduit to prevent mechanical damage before it enters the building.  The visible conduit should be made of either galvanized steel or gray plastic, rated for the purpose.

Electric charge is a property of certain subatomic particles, which gives rise to and interacts with the electromagnetic force, one of the four fundamental forces of nature. Charge originates in the atom, in which its most familiar carriers are the electron and proton. It is a conserved quantity, that is, the net charge within an isolated system will always remain constant regardless of any changes taking place within that system.  Within the system, charge may be transferred between bodies, either by direct contact, or by passing along a conducting material, such as a wire.  The informal term static electricity refers to the net presence (or ‘imbalance’) of charge on a body, usually caused when dissimilar materials are rubbed together, transferring charge from one to the other.

The main circuit breaker, usually located inside the main panel at the top, shuts off all of the electricity to the house. In a dire emergency, this is the one to turn off. Otherwise, shut off only the breaker that serves the problem circuit-that way, other parts of your house will continue to have lights and power. The main circuit breaker does not shut off the wires that run from the main panel breakers to the electric meter-these are always hot.

A typical home has several circuits to deliver electricity to different areas of the property, as shown in the illustration below. All of these so-called branch circuits originate at a service distribution panel, which has two hot bus bars and one neutral bus bar.  Depending on the amount of electricity a given circuit needs to deliver, it may attach to only one hot bus bar and the neutral bus bar or to both hot bus bars. For example, a circuit that delivers 120 volts connects to one hot bus bar and the neutral bus bar, while a circuit that delivers 240 volts connects to both hot bus bars.

Many people use the term “Romex” when referring to type-NM cable. Romex is a trademark name that has come into common usage  for plastic-covered wires, but type-NM just means “non-metallic,” and also applies to other cable styles.   The earliest NM cables were, in fact, rubber-insulated copper conductors bound together as an assembly, with a woven-cloth sheathing. Originally approved by the NEC in 1928 as replacement for knob-and-tube wiring, it became the most common residential wiring used from the late 1940s, up to the introduction of modern thermoplastic (Romex) type wiring of the early 1960s.  Prior to 1985, standard NM was rated for 60-degree applications, which was increased to 90 degrees and is now marked NM-B.

The Barrie Home Inspector checks your electrical panel and home circuits during your home inspection.   He can identify illegal connections or poorly installed wiring.   With all the Do-It-Yourself work being done in homes today, it is a good investment to have your home inspected by a professional prior to purchasing.  Some sellers hide defective workmanship and the fact that work was done without a permit and hope that the buyer does not ask or notice the deficiencies.  Be a smart consumer protect yourself with a Professional Home Inspection.

Inspecting Commercial Buildings and Their Power Supply

Inspecting Commercial Buildings and Their Power Supply

In electrical engineering, single-phase electric power refers to the distribution of alternating current electric power using a system in which all the voltages of the supply vary in unison. Single-phase distribution is used when loads are mostly lighting and heating, with few large electric motors. A single-phase supply connected to an alternating current electric motor does not produce a revolving magnetic field; single-phase motors need additional circuits for starting, and such motors are uncommon above 10 or 20 kW in rating.
In contrast, in a three-phase system, the currents in each conductor reach their peak instantaneous values sequentially, not simultaneously; in each cycle of the power frequency, first one, then the second, then the third current reaches its maximum value. The waveforms of the three supply conductors are offset from one another in time (delayed in phase) by one-third of their period.

Defining the Terms

Amps vs. Volts:
Think of electricity as water flowing through a pipe. The amperage is analogous to the amount of water flowing through the pipe. Amperage is also called current. Larger diameter wires can handle more current, just as larger pipes can handle more flow.

Voltage is analogous to pressure, the force which moves the water through the pipe. A small pump (low voltage) would produce less pressure than a big pump (high voltage).

In most buildings the voltage will either be 208 volt (low voltage) or 600 volt (high voltage). The critical question is how much voltage and amperage the system is rated at, or in other words, how much equipment can I use in the building?

208 Volt vs. 600 Volt:
Most modern buildings are equipped with 600 volt services. Equipment such as air conditioning units (over 5 tons), larger exhaust fans, electric heaters, and some lighting will utilize 600 volts. However, standard outlets and most lighting operate at 208 volts.

In North America, individual residences and small commercial buildings with services up to about 100 kV·A (417 amperes at 240 volts) will usually have three-wire single-phase distribution, often with only one customer per distribution transformer. In exceptional cases larger single-phase three-wire services can be provided, usually only in remote areas where poly-phase distribution is not available. In rural areas farmers who wish to use three-phase motors may install a phase converter if only a single-phase supply is available. Larger consumers such as large buildings, shopping centers, factories, office blocks, and multiple-unit apartment blocks will have three-phase service. In densely populated areas of cities, network power distribution is used with many customers and many supply transformers connected to provide hundreds or thousands of kV·A, a load concentrated over a few hundred square meters.

Buildings equipped with 600 volt services will always have a transformer to reduce the 600 volts to 208 volts for the main building panels. These transformers are generally located near the main electrical service entrance.

When comparing the amount of power available for different voltages, a 200 amp, 600 volt service has nearly three times the power of a 200 amp, 208 volt service.

This is of less importance. All 208 volt and 600 volt services are three phase. This means there are three power wires coming into the building.

Single phase services may be found in older, smaller buildings and are found exclusively in houses.

In some older buildings you can find a single phase and a three phase service. This is usually identifiable, on the outside, by two separate services leading to the building.

Determining Amperage of Service

When you are inspecting the electrical room, the two items of information you are looking for; the are amperage and voltage. The presence of a transformer in the electrical room is usually indicative that it is 600 volts. They do make transformers that can used to step up a 208 volt service to 600 volts, for a specific piece of equipment.

What you should typically see is a small conduit (high voltage, low current) going into the transformer and a larger conduit (low voltage, high current) coming out and leading to a breaker panel or a splitter panel.

The ratings on the switches and splitter panel are not to be relied on; they only tell you the maximum amount of current or voltage the equipment can handle. Do not rely on the rating of the hydro meter(s), for the same reason.

The best way to verify the amperage is to open the door of the main power switch and read the rating of the main fuses. This is sometimes impossible to do without turning the power off, but is always dangerous, unless you know what you are doing. Even with the power off, half the box is live. You can end your real estate career, right there in somebody’s electrical room.

Reading the gauge (size) of the main power wires (in the meter cabinet or main splitter panel) can also help to determine the amperage of the service. The gauge number is typically printed on the wire sheathing. Common wire gauge sizes, for copper conductors and the allowable amperages are as follows:

Wire Gauge Allowable Amperage
3 100 amps
000 200 amps
350MCM 300 amps
500MCM 400 amps

Fluorescents Lights and Mercury Scare?

Fluorescents Lights and Mercury Scare? The poster-child for the anti-fluorescent bulbers is Brandy Bridges, a mother in Maine who broke a bulb in her daughter’s bedroom a couple years back.

Bridges, aware the bulbs contained mercury, called state officials, who came over, did tests, and told her to have the room cleaned by a hazardous waste crew – to the tune of over $2,000. Maine officials eventually came to her house and cut out the carpet.

This story has been widely circulated on the Internet, and sharp criticism of the government mandate continues today from email chain letters to rants on Capitol Hill.

When it comes to safety, they say the amount of mercury in a fluorescent bulb is so small it should not present a health risk. According to the Environmental Protection Agency, the average fluorescent light bulb contains about 4 milligrams of mercury, over 100 times less than found in an old mercury thermometer.

Consumer Reports just did extensive testing of the bulbs and found that many contain even less mercury – some had just 1 milligram.

“It’s not something to panic about,” said Celia Kuperszmid Lehrman, deputy home editor at Consumer Reports. “Tube fluorescents like we all have in our offices and schools have mercury too, and it’s not like they evacuate a school every time a bulb breaks.”

Still, the bulbs should be handled with care if broken. EPA recommends several steps including cleaning up the glass with cardboard or another item that can be disposed of after, opening the window, and putting the remnants in an outside garbage can.

If your town collects other household hazardous waste like batteries, paint or cleaning supplies, then you should dispose of the bulbs in the same manner. Home Depot and Ikea will recycle any old fluorescent bulbs, no mater where they were purchased.

Also, if the light is close to small children or pets that may easily knock it over, it’s probably best to use another type of bulb. Efficient, mercury-free incandescents like halogen lights, as well as LED lights will still be available after the new efficiency standards kick in.

The benefits of using fluorescent bulbs, experts say, far outweighs any mercury risk.

When it comes to mercury content, a fluorescent bulb ends up putting far less mercury into the environment compared to all the extra electricity required to run an inefficient bulb – four times less mercury, according to Noah Horowitz of the Natural Resources Defense Council.

If the whole country switched to fluorescents, says Horowitz, it would eliminate the need to build 30 new coal power plants and save as much electricity as used by all the homes in Texas.

Then there’s the cost savings. Consumer reports estimates that each incandescent replaced with a $1.50 fluorescent will save an individual $56 in electricity costs over the life of the bulb.

“You’d be hard pressed to find a better deal for your wallet or the environment,” said Horowitz.

Still, some people remain unconvinced.

For starters, many say if fluorescent bulbs were really better, people would buy them on their own.

For her part Bridges, contacted at her home in Maine, says she’ll never go back to fluorescent bulbs and has little faith in experts telling her what’s safe.

“Remember, at some point lead paint wasn’t a big deal either,” she said.\

For more home owner tips and advice, visit the Barrie Home Inspectors blog on Home Owners Tips and Maintenance.